Advisory Details

January 7th, 2015

Schneider Electric ProClima ATX45 SetBodyAttribute Remote Code Execution Vulnerability

ZDI-15-004
ZDI-CAN-2479

CVE ID CVE-2014-8512
CVSS SCORE 7.5, AV:N/AC:L/Au:N/C:P/I:P/A:P
AFFECTED VENDORS Schneider Electric
AFFECTED PRODUCTS ProClima
TREND MICRO CUSTOMER PROTECTION Trend Micro TippingPoint IPS customers are protected against this vulnerability by Digital Vaccine protection filter ID ['16621']. For further product information on the TippingPoint IPS: http://www.tippingpoint.com
VULNERABILITY DETAILS


This vulnerability allows remote attackers to execute arbitrary code on vulnerable installations of Schneider Electric ProClima. User interaction is required to exploit this vulnerability in that the target must visit a malicious page or open a malicious file.

The specific flaw exists within the ATX45.ATX45Ctrl.1 ActiveX control in Atx45.ocx. The control does not check the length of an attacker-supplied string in the SetBodyAttribute method before copying it into a fixed length buffer on the heap. This allows an attacker to execute arbitrary code in the context of the browser process.

ADDITIONAL DETAILS Schneider Electric has issued an update to correct this vulnerability. More details can be found at:
https://ics-cert.us-cert.gov/advisories/ICSA-14-350-01
DISCLOSURE TIMELINE
  • 2014-08-13 - Vulnerability reported to vendor
  • 2015-01-07 - Coordinated public release of advisory
CREDIT Brian Gorenc - HP Zero Day Initiative
BACK TO ADVISORIES