Advisory Details

September 15th, 2021

Schneider Electric Struxureware Data Center Expert Command Injection Remote Code Execution Vulnerability

ZDI-21-1072
ZDI-CAN-13553

CVE ID CVE-2021-22795
CVSS SCORE 8.8, AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H
AFFECTED VENDORS Schneider Electric
AFFECTED PRODUCTS Struxureware Data Center Expert
VULNERABILITY DETAILS

This vulnerability allows remote attackers to execute arbitrary code on affected installations of Schneider Electric Struxureware Data Center Expert. Authentication is required to exploit this vulnerability.

The specific flaw exists within the testRepository method. The issue results from the lack of proper validation of a user-supplied string before using it to execute a system call. An attacker can leverage this vulnerability to execute code in the context of root.

ADDITIONAL DETAILS Schneider Electric has issued an update to correct this vulnerability. More details can be found at:
https://us-cert.cisa.gov/ics/advisories/icsa-21-257-03
DISCLOSURE TIMELINE
  • 2021-04-30 - Vulnerability reported to vendor
  • 2021-09-15 - Coordinated public release of advisory
CREDIT David Yesland